Years ago, when we were busy installing biomass boilers we were excited and proud to be helping the UK heating profile change to one of sustainable practices and renewable fuels.


This is the second in a series of posts about heating network management – please follow Minibems to receive notification of the upcoming posts.


After a few heating networks were up and running we were able to analyse the results. We had an unpleasant surprise; overall system efficiency over the course of a year would be around 45% to 55%, well below our expectations.

Why are heating networks so inefficient?

The current design template is to deliver a constant temperature and constant flow of heat around the network. This is generally set at a temperature and flow rate that will meet the worst case scenario; when it is very cold outside.

Generally, that is defined as a few degrees Celsius below zero, depending on the location of the site in the UK.

That means that a fixed amount of energy is being converted into heat, regardless of whether the demand for that amount of energy is there or not. The hot water in the pipework is not actually leaving much of its heat at the point of use. So, rather than being used to heat the homes, offices and provide domestic hot water, that energy is being lost in the distribution pipework or going up the flue.

As you can imagine, the majority of time heating is required worst-case scenario conditions are not present e.g. it may be chilly but not freezing.

At these times the boiler is constantly cycling (turning on and off) to keep the water in the system at the constant set temperature but, as the actual heating demand is low, only a small amount of heat leave via the heat emitters e.g. radiators. The temperature of the water flow is much higher than need be.

Top section demonstrate narrow difference between the flow and return temperatures. Middle Section shows, ‘cycling’. Bottom section shows excessive use of electrical fans leading to wear and tear and higher energy bills.


 

Meanwhile by pushing the flow of water around the system so quickly (at a constant volume) the hot water does not have the chance to spread the heat from the radiator, cool down, and return to the boiler at a lower temperature.

If the system was working to standard design parameters the difference between flow (outgoing water) and return (water going back to the boiler) temperature would be 11 degrees Celsius, whereas at best we generally see a difference of 5 or 6 degrees Celsius. Very efficient systems have a temperature difference between flow and return of over 20 degrees Celsius.

Our next article will look at the ways to optimise a heat network, delivering a much larger temperature difference between the flow and return and saving energy.

 

When was the last time you checked your boiler flow and return temperatures?


This is the second in a series of posts about heating network management – please follow Minibems to receive notification of the upcoming posts.

Next Article: Delta T- Let’s be having you, Or: Optimisation – What is a constantly optimisable heat network?

To learn more please see our brochures or email Ben Carter.

Hello! These posts reflect the Minibems point of view, our expertise and our aspirations. We are interested in hearing from anyone who works and thinks about this sector. We want to engage with as many stakeholders and colleagues as possible help us to learn and develop our solutions.

Latest resources, blogs & events

Get in touch

Call the Minibems
experts on 01392 241 243 for further information.

For heating and billing customer support call 0800 520 0135.
Email Minibems info@minibems.com